The
short answer to the question of sample interval is to sample between 4
and 10 times faster than the process dead time. 4 times faster being barely
adequate and 10 times faster being the best.
Ideal Sample Interval = (Process Dead Time)/10. It is better to err on
the side of being too fast. This applies both for what your industrial
digital controller should sample at and how fast to collect data for analysis,
modeling and PID tuning.
Sampling
Too Slow
Now for a more in depth look. If you don’t collect the data fast
enough then you will be “hiding” data from the controller
or analysis software. Imagine if you attempted to drive your car by looking
at the road once every 5 seconds.
The limiting factor in process control is dead time. Sampling adds about
1/2 the sample time to the process as dead time. The red line in the plot
below shows the optimal response of a loop to a disturbance. The controller
in this loop is sampling 3 times slower than the process dead time. (process
dead time = 10 sec., time constant = 30 sec. Controller sampling at 30
sec.) The controller does nothing about the upset until a time of 30 leaving
20 seconds of time when it was blind to the upset.
The
cyan line in the plot shows the same loop with the same disturbance, but
this time the controller is sampling faster. The controller is now sampling
at the same rate as the dead time. The controller tuning is the same in
both loops. The response is 30% faster simply because we made the sample
interval faster.
The
green line in the plot below, again is for the same loop and disturbance,
but this time with a sample interval at 10 times faster than the process
dead time. This sample interval is now properly set. The response is almost
twice as fast as that with the sample time equal dead time. About 20%
of the improvement in response was because we were able to adjust the
tuning to be faster. The tuning of all three loops has roughly the same
robustness or sensitivity to process changes. If you use the ExperTune
Loop Analyzer, the software checks sample interval and recommends the
optimal interval to use.
Aliasing and Sampling Hyper-Fast
Now lets look at why some people feel they need to sample extremely fast
- at times approaching 1 millisecond for loops that have dead times of
2 or 3 seconds. This would be sampling at 2000 times faster than the dead
time.
The phenomena they are trying to avoid is called aliasing. Aliasing or
“ghost signals” are a real problem. Take a look at the plot.
We are sampling the cyan sign wave signal at a rate shown by the gray
vertical lines. At each sample interval, we get an actual value shown
by a red blob in the graph above.
When you connect the dots, you get the slow sine wave shown in yellow.
But this slow sine wave is not in the original signal. The yellow sine
wave reveals a ghost or alias signal that is not in the analog signal.
One attempt at solving the aliasing problem is to sample extremely fast
and then apply a digital filter on the hyper-collected data. This would
eliminate aliasing in frequencies below the hyper-sampling frequency but
would not eliminate aliasing occurring at higher frequencies
On higher frequency noise, aliasing signals would still come through.
Extremely fast data collection equipment is more costly, and the amount
of data collected uses lots of hard drive space, making it hard to transfer
the data to different machines and takes more time to process. Isolating
the signals that are sampled fast adds additional cost, so the tendency
is to omit this safety hardware when hyper-sampling.
Collecting data faster than control loop is going is usually wasted data
since the controller cannot react to the resultant tuning.
Fortunately the complete solution for aliasing is simple and has been
around a long time. Simply add an analog filter or anti-aliasing filter
to the signal before it is digitized. The analog filter completely decimates
higher frequency signals that leaked through on the previous hyper-sampling
attempt. Most I/O for most distributed control systems have analog anti-aliasing
filters. They may simply be called a filter. In much I/O, analog filters
are set to reduce noise most drastically in the 50-60 Hz range. In the
above example if we apply a simple first order filter with a time constant
of 1/2 the sample interval the aliasing gets reduced by a factor of 6,
reducing the level probably below the resolution of the analog to digital
converter.
Conclusions
Sampling at the proper rate will allow optimal control of your loop. ExperTune’s
Loop Tuner/Analyzer, automatically checks your loop’s sample interval
and tells you if it needs to be changed.
While there are many practical and economic advantages to using temperature
transmitters, the most basic are to ensure measurement integrity and to
convert a temperature sensor’s low-level (ohm or mV) signal to a
standard 4-20mA current signal that can be readily accepted by a monitoring
and control system, such as a DCS or PLC. Advancing technology has made
the use of temperature transmitters affordable, even in cost-sensitive
applications. Here are few things to consider when choosing one.
1. Back of Panel or Local Installation
Perhaps the most fundamental consideration when specifying a temperature
transmitter is the environment in which it will be installed. If the distance
between the sensor measurement and the control room is relatively short
and free of plant electrical “noise”, temperature transmitters
can be inexpensively installed in the control room, with sensor extension
wires leading to them. These transmitter configurations are called DIN-style
or rail- mount housings (Figure 1). For economy reasons, multiple high-density
DIN-style transmitters are installed on a mounting rail in a multi-unit
protective enclosure, and are powered by a common power supply.
Figure
1. Rail-mount housings are typically mounted on a surface or in
a multi-unit protective enclosure. |
If
a long distance exists between the sensor and the control room, or if
plant noise will adversely affect the sensor’s relatively “weak”
low level signal, the temperature transmitter should be installed as close
to the sensor as possible. This will allow the sensor signal to be conditioned
and converted to a more robust 4-20mA signal better able to withstand
long-distance transmission through a “noisy” plant.
For these applications, transmitters are installed individually in field-mountable
enclosures called connection or thermowell heads (Figure 2). To accommodate
corrosive, caustic, hazar
Figure
2. Field-mount housings accommodate corrosive, caustic, hazardous,
hose down or just plain nasty weather conditions. |
dous,
hose down, or just plain nasty weather conditions, connection heads come
in a variety of shapes and materials including aluminum, stainless steel,
iron, and plastic. Where ambi-surement will be. Much worse, with fixed
range transmitters, if you must change to a different sensor type.
Microprocessor-based universal transmitters offer a vast array of operational
advantages at prices just slightly higher than many of their restrictive
fixed range counterparts. Most important of these is the ability to be
set up to handle a wide range of different sensor types and temperature
ranges. This may include thermocouples (J, K, E, T, R, S, B, N, and C)
and RTDs (2-, 3-, and 4-wire; Pt, Cu and Ni; 10 to 1000 ohm), and temperature
ranges within –328 to 1562°F (-200 to 850°C). Universal
transmitters can be set to monitor any range within the sensor’s
established curve. Therefore, you can set the transmitter to “concentrate”
on the exact range important to your process.
One transmitter type can be specified and stocked to handle every application
in the facility. If you (like most) use many different sensor types, have
had to change the type of sensor you use, or are just not certain what
may happen in the future, universal transmitters are a much more flexible
way to go.
Figure
3. For surface measurements, the sensor and transmitter may be clamped,
strapped, bolted or welded directly to the measurement point.
|
3. Configuration Method
Available universal temperature transmitters can be configured using on-board
controls, hand-held configurators, and/or with PC software. On-board controls
provide the advantage of not having to rely on external devices to perform
set up. However, the configuration options available are sometimes very
limited.
Hand-held configurators are usually associated with smart instruments,
such as smart HART® temperature transmitters. They provide the advantage
of being able to re-configure the transmitter from any convenient termination
point along the 4-20mA loop. The disadvantages are that hand- elds can
be less than intuitive, expensive (over $2500), and sometimes can only
be used with one type or class of instrument.
PC configuration is the most versatile, and by far the easiest and fastest
to use (Figure 4). All operating parameters, even complex custom sensor
linearization tables, can be easily selected from a software window and
downloaded to the transmitter in a few minutes. A great PC costs less
than many hand-helds, and can be used for numerous other purposes. The
only drawback is that the transmitter must be taken to the PC, or a laptop
must be taken to the transmitter, for configuration.
Figure
4. PC software allows transmitter
configuration in just a few minutes. |
4.
Accuracy and Stability
Temperature transmitters differ greatly in measurement accuracy. At the
low end, you can expect accuracies of ±1°F. At the high end,
some transmitters deliver amazing accuracies of ±0.025°F. Many
factors can influence overall accuracy including: input accuracy, output
accuracy; resolution; linearity; load effect; line voltage effect; cold
junction compensation (for thermocouples); repeatability; ambient temperature
effect; EMI/RFI effect; and sensor lead resistance effect. Complicating
matters, the way that stated accuracy is determined differs from manufacturer
to manufacturer.
When doing accuracy comparisons, keep in mind that some vendors use the
term linearity in place of accuracy. Others will state that the accuracy
specification includes linearity and repeatability, and assumes errors
caused by fluctuating ambient temperature conditions. Still other specifications
are stated in terms of a selected temperature range, temperature reading,
or measurement span. Be sure to read the fine print so that you can properly
determine the accuracy of a given transmitter under the conditions it
will operate. The degree of accuracy required for your application is,
of course, dependent on the nature of the process itself. In general,
the higher the accuracy is, the more certain the outcome of nearly every
process.
Whereas accuracy is the level of uncertainty of a transmitter’s
output at a given time, stability is the uncertainty of a transmitter’s
or sensor’s output over a period of time. Stability (usually specified
as a percent of temperature span per year) will help you tell how often
your system will need routine calibration. Typical long-term stability
specifications provided by manufacturers range from 6 months to 5 years.
5. Sensor Selection
Your temperature transmitter supplier should be able to recommend the
best sensor for your application. In general, an RTD will give you a more
accurate, stable temperature measurement than a thermocouple (T/C), provided
the somewhat more fragile RTD can withstand the environment.
PC
configuration is the most versatile, and by far the easiest and
fastest to use (Figure 4). All operating parameters, even complex
custom sensor linearization tables, can be easily selected from
a software window and downloaded to the transmitter in a few minutes.
A great PC costs less than many hand-helds, and can be used for
numerous other purposes. |
An
RTD or T/C output will change due to temperature cycling, temperature
swings, corrosion, lead wire degradation, moisture, and contamination.
Where possible, use 4-wire RTDs, and specify a temperature transmitter
that is able to accept a “true” 4-wire RTD input. The advantage
is that the fourth wire in a RTD circuit effectively cancels out errors
due to resistance imbalances between the leads. Every ohm of imbalance
in an RTD’s lead wires results in as much as a 2.5°C measurement
error.
6.
RFI/EMI Protection and Signal Isolation
Always specify a transmitter with a stated RFI/ EMI immunity specification.
The effects of Radio Frequency Interference (RFI) and Electromagnetic
Interference can cause unpredictable and non-repeatability degradation
in transmitter performance and accuracy, and even complete instrument
malfunction.
Even if you think your environment is “noise free”, consider
just a few of the sources of possible RFI/EMI interference: mobile and
stationary radio, television and hand-held (walkie-talkies) transmitters;
transformers; ac and dc motors; large solenoids or relays; and even fluorescent
lights.
7. Diagnostic Capabilities
Temperature transmitters, even simple fixed– range analog ones,
are capable of providing basic diagnostics in the form of driving their
4- 20mA output upscale or downscale on loss of sensor input. This is to
alert you of a sensor burn out.
Temperature transmitters with intelligent diagnostic capabilities are
able to go a step further. In addition to upscale/downscale drive, they
continually monitor the sensor, and if a wire breaks or otherwise stops
sending a signal during operation, can show you which wire has broken
via an error message either on an integral digital display (in the case
of indicating transmitters) or using their PC configuration software.
Specific fault messages eliminate the work of removing the sensor or checking
all of the lead wires to diagnose a problem (Figure 5).

Figure
5. Some transmitters provide specific fault messages that speed
diagnosing the exact sensor problem. |
8. Digital Communications
The vast majority of temperature transmitters installed and still being
specified use 4-20mA signals for interface with a control device or system.
4-20mA is standard, it’s simple, it’s trusted, and it works.
This is changing as users realize the benefits of implementing available
digital protocol strategies such as Foundation Fieldbus, HART, and Profibus.
The most visible advantage includes the ability to multidrop multiple
transmitters onto one twisted pair, which saves wiring and installation
costs. A second important advantage is that digital communications allows
the transmitter to deliver valuable loop diagnostic information directly
to the system. This can be used to alert the user of sensor and transmitter
problems, and even alert of potential problems for preventative maintenance.
The drawback is that in addition to new all digital communicating transmitters,
you also have to commit to a control system that is able to accept digital
communication protocol data.
9.
Agency Certifications
Hazardous area certifications are usually not a choice, but a requirement.
Worldwide agencies, such as Factory Mutual (FM) and UL (Underwriter’s
Laboratories), study the design, test and certify instruments as generally
being safe to install in hazardous areas. Hazardous areas typically include
those where explosive gases, such as hydrogen or acetylene, may be present.
If you are installing the instrument in a hazardous area, you need to
make sure that you specify one that is rated for use in that ‘classified’
area. This is typically signified by a coding system that identifies the
instrument’s hazardous area rating. For example, if an instrument
is FM approved for use in an explosion- proof area, the coding on the
unit should look like this: Class I, Division I, Groups A, B, C, D.
10. Special Functionality
It should come as no surprise that temperature, being the most measured
process variable, would have dozens, if not hundreds, of very unique application-specific
requirements. Fortunately, market demand has led temperature transmitter
manufacturers to address these needs with very specialized features. This
may include integral digital displays that can be programmed to show application-specific
operating parameters (Figure 6); the ability to build custom linearization
tables for non-standard sensor inputs; and advanced sensor trimming techniques
that result in phenomenal measurement accuracies of up to ±0.025°F.
If you need it, it’s probably available.
|
Figure
6. Special functions, like a customizable display, help meet unique
application requirements |
|
|